NEC Voltage Drop Calculator

US NEC 2026 voltage drop calculator using Chapter 9 Tables 8 & 9 impedance for 1-phase, 3-phase, and DC runs.

Circuit Parameters

PRESETS M1–M4
PHASE / SYSTEM
METAL
Enter a positive source voltage (1–15,000 V).
Enter a load current between 0.1 and 10,000 A.
Enter a one-way length between 0.1 and 20,000 ft (6,096 m).
Enter a power factor between 0.10 and 1.00.

CH-1 · Live Voltage Drop Telemetry

NEC CH. 9 TABLES 8 & 9
TOTAL VOLTAGE DROP
4.70 V (1.96%)
PASS ≤ 3% Branch (NEC 210.19) PASS ≤ 5% Total (NEC 215.2)
NEC DROP METER (0% – 8%) 1.96% of 240V
0% 3% BRANCH 5% TOTAL 8%
MAIN PANEL 240 V 1-PH AC 75°C · PF 1.00 HOT RTN 6 AWG Cu PVC CONDUIT · 100 ft ONE-WAY ΔV 4.70 V (1.96%) NEC PASS ≤ 3% · Z_eff 0.4900 Ω/kft LOAD TERMINAL 235.30 V 48 A LOAD DELIVERED AT LOAD
Voltage at Load
235.30 V
Impedance (Zeff)
0.4900 Ω/kft
Resistance (R)
0.4900 Ω/kft
Reactance (XL)
0.0510 Ω/kft
6 AWG Copper meets the NEC 3% branch circuit voltage drop guideline (1.96%). Minimum gauge for ≤ 3% is 6 AWG.

Copper vs. Aluminum · Side-by-Side NEC Compliant Comparison

NEC 310.16 (≤75°C) + CH. 9 ≤ 3% VD
Copper (Cu) · THHN/THWN-2 ACTIVE METAL
MIN COMPLIANT AWG 6 AWG Cu
Exact Drop
4.70 V (1.96%)
Delivered V
235.30 V
Est. Material / 100 ft
$260–$350
Aluminum (Al) · XHHW-2
MIN COMPLIANT AWG 4 AWG Al
Exact Drop
4.90 V (2.04%)
Delivered V
235.10 V
Est. Material / 100 ft
$128–$184
Aluminum (4 AWG) saves est. $132–$166 / 100 ft (~49% lower conductor cost) vs. 6 AWG Copper — verify larger conduit bore & NEC 110.14 Cu/Al-rated lugs.
Minimum gauges satisfy both NEC Table 310.16 base ampacity (≤75°C lugs & 240.4(D) cap) and Chapter 9 voltage drop. Material estimate reflects 2 circuit conductors per 100 ft using typical US retail reference ranges; verify 125% continuous load, ambient/bundling derating, and conduit bore.

Saved Circuit Schedule & Multi-Run Comparison

0 / 6 RUNS SAVED

No circuits logged yet. Click + Save Run above to compare up to 6 branch circuits or feeders side-by-side, export a CSV schedule, or print an NEC field sheet.

Worked NEC 2026 Voltage Drop Examples

Pre-calculated using NEC Chapter 9 Table 9 AC resistance and reactance at 75°C. Use these field benchmarks to sanity-check branch circuits and feeders before pulling wire.

WireCalcs NEC 2026 Voltage Drop Calculator live output showing a 240V 48A EV charger on 100 ft of 6 AWG copper wire passing at 4.70 V (1.96%) with reactive circuit schematic and segmented LED meter
Live WireCalcs instrument benchmark: 240V 48A EV charger on 100 ft of 6 AWG copper THHN in PVC conduit showing 4.70 V (1.96%) voltage drop, live schematic, and NEC 3% pass status.
NEC Chapter 9 Table 9 Worked Examples (Single Set, 75°C)
Circuit Scenario System Load 1-Way Run Conductor Drop (V) Drop (%) NEC Status Min ≤3%
Garage 20A Branch (120V) 120V 1-Ph 16 A 100 ft 12 AWG Cu 6.40 V 5.33% >5% 8 AWG
48A EV Charger (240V) 240V 1-Ph 48 A 100 ft 6 AWG Cu 4.70 V 1.96% PASS ≤3% 6 AWG
Detached Shop 100A Subpanel 240V 1-Ph 80 A 150 ft 1 AWG Al 6.04 V 2.52% PASS ≤3% 1 AWG
Well Pump 240V (250 ft) 240V 1-Ph 15 A 250 ft 10 AWG Cu 7.85 V 3.27% 3–5% 8 AWG
Commercial 208V 3-Ph Feeder 208V 3-Ph 100 A 200 ft 1/0 AWG Cu 4.54 V 2.18% PASS ≤3% 1 AWG
Industrial 480V 3-Ph Motor 480V 3-Ph 65 A 300 ft 4 AWG Cu 9.97 V 2.08% PASS ≤3% 4 AWG

NEC Chapter 9 Formula & Engineering Scope

1-Phase / DC & 3-Phase Equations

V_drop (1-Ph / DC) = (2 × L × I × Z_eff) / (1000 × N) V_drop (3-Ph) = (√3 × L × I × Z_eff) / (1000 × N) Z_eff = R_ac × cos(θ) + X_L × sin(θ)

Where L is one-way length in feet, I is load amperes, N is parallel sets per phase, and R_ac, X_L come directly from NFPA 70 (NEC) Chapter 9 Table 9 (75°C base with Table 8 Note 2 temperature adjustment).

Limitations & When Not to Rely on This Estimate Alone

  • Ampacity is checked separately: Meeting 3% voltage drop does not guarantee Table 310.16 ampacity compliance—verify both in our NEC Wire Size Calculator.
  • Motor starting inrush: Steady-state FLA is used here; large motors with locked-rotor currents (6× FLA) require dedicated starting voltage dip checks.
  • NEC 250.122(B) EGC upsizing: When you upsize phase conductors for voltage drop, remember to proportionally upsize the equipment ground.
  • Energy code & workplace rules: Commercial building feeders must also satisfy state energy codes tracked by the US DOE Building Energy Codes Program (ASHRAE 90.1 / Title 24) and OSHA 29 CFR 1910.303 workplace electrical standards.

Field Questions & NEC Notes

Why does NEC Chapter 9 Table 9 give a different drop than the simple 2KIL/CM formula?

The older 2 × K × I × L / CM shortcut uses a fixed DC resistivity constant (K ≈ 12.9 for copper) and ignores AC skin effect, steel conduit eddy losses, and inductive reactance (XL). For conductors 1/0 AWG and larger—especially inside steel EMT or RMC—reactance adds substantial voltage drop that Table 9 captures via Zeff = R cos θ + XL sin θ.

Are the NEC 3% branch and 5% total voltage drop limits mandatory?

In NEC 210.19(A) Informational Note No. 3 and NEC 215.2(A)(2) Informational Note No. 2, the 3% branch / 5% combined limits are informational recommendations rather than mandatory code text—except where specifically mandated (such as NEC 647.4(D) sensitive electronic equipment at 1.5%/2.5%, NEC 695.7 fire pumps at 15% starting / 5% running, or state energy codes like California Title 24 and ASHRAE 90.1).

If I upsize ungrounded conductors for voltage drop, must I upsize the equipment grounding conductor (EGC)?

Yes. Per NEC 250.122(B), whenever ungrounded phase conductors are increased in circular mil area for voltage drop, the equipment grounding conductor must be increased proportionately according to the circular mil ratio of the installed phase conductor to the minimum code-required phase conductor.

Should I enter one-way distance or total wire length?

Enter the one-way circuit run length from the panelboard or transformer to the load. The calculator automatically multiplies by 2 for single-phase and DC circuits (accounting for out-and-back return current) and by √3 (1.732) for balanced three-phase circuits.