NFPA 70 · NEC 2026 Chapter 9 Tables 1, 4 & 5 LOCAL SOLVER · ZERO LOGIN

NEC Conduit Fill Calculator

NEC 2026 mixed-conductor conduit fill calculator with CAD bore view, Note 7 round-up, and jam-ratio checks.

Raceway & Conductors

TABLES 4 & 5
Conductors in Raceway
Size Insul. Qty Unit (in²) Subtotal
6 AWG THHN/THWN-2 3 0.0507 0.1521
10 AWG THHN/THWN-2 1 0.0211 0.0211

CH-2 · CAD Bore Cross-Section & Fill

53% / 31% / 40% / 60%
#6 #6 #6 #10 ID 0.824" · FILL 32.5% / 40% MAX
THHN XHHW-2 RHW-2 Bare
CALCULATED CONDUIT FILL
32.5% Fill
PASS · 4 Wires (40% Limit)
BORE FILL SCALE (0–70%) 32.5% / 40% limit
Minimum Legal Size
3/4" EMT
Total Wire Area
0.1732 in²
100% Bore Area
0.533 in²
Max Allowed Area
0.2132 in² (40%)
Compliant under NEC Chapter 9 Table 1 (40% fill rule). Remaining usable area: 0.0400 in².

Mixed Conductor Fill Benchmarks (NEC Chapter 9)

Annex C lookup tables only work when every conductor in the pipe has the exact same gauge and insulation. Whenever you mix phase wires, reduced neutrals, or bare grounds, you must sum individual Table 5/Table 8 square-inch areas against Table 4.

Worked Mixed-Wire Conduit Fill Checks
Installation Conductors Wire Area NEC Limit Actual Fill Status Min Size
50A Range Feeder (3/4" EMT) 3× 6 AWG THHN/THWN-2 + 1× 10 AWG THHN/THWN-2 0.1732 in² 40% 32.5% PASS 3/4"
100A Subpanel (1-1/4" PVC 40) 3× 1 AWG XHHW-2 + 1× 6 AWG Bare Cu 0.4872 in² 40% 33.5% PASS 1-1/4"
200A Service (2" PVC Sch 80) 3× 4/0 AWG XHHW-2 + 1× 4 AWG Bare Cu 1.0015 in² 40% 34.8% PASS 2"
Two #10 THHN (1/2" EMT — 31% Rule) 2× 10 AWG THHN/THWN-2 0.0422 in² 31% 13.9% PASS 1/2"

NEC Chapter 9 Table 1 Rules & Jam Ratio Limits

Area Summation Formula

Fill % = (Σ [Qty_i × Area_Table5_i] / Area_Table4) × 100 Limits: 1 wire ≤ 53% · 2 wires ≤ 31% · 3+ wires ≤ 40% · Nipple ≤ 60% · Note 7 (≥0.80 round-up)

Need identical-wire count matrices instead? Jump directly to the NEC Annex C Conduit Fill Chart, PVC Sch 40 vs. Sch 80 Chart, or EMT Table C.1 Chart. Before ordering raceway for long feeders, check conductor upsizing in the NEC Voltage Drop Calculator.

Limitations & Field Pulling Factors

  • Multiconductor cables (NM-B, UF-B, tray cable): NFPA 70 Chapter 9 Note 9 requires treating each elliptical cable as a circle whose diameter equals its major axis—do not enter individual internal wire gauges for jacketed cables.
  • Jam ratio (D/d = 2.8–3.2): Even when fill is under 40%, three equal wires pulled through 90° bends can wedge side-by-side inside the conduit.
  • Ampacity bundling & workplace rules: Filling a conduit to 40% with more than 3 current-carrying conductors triggers NEC Table 310.15(C)(1) derating; verify workplace conduit rules in OSHA 29 CFR 1910.305.

Field Questions & NEC Notes

Why does NEC Chapter 9 Table 1 allow only 31% fill for 2 wires but 40% for 3 or more wires?

Two circular conductors inside a circular raceway cannot nest symmetrically around the center—they sit side-by-side and wedge tightly at bends if the fill exceeds roughly 31%. Three or more wires form a stable triangular or circular bundle that pulls cleanly up to 40% cross-sectional fill.

Do equipment grounding conductors count toward conduit fill?

Yes. Per NEC Chapter 9 Note 3, equipment grounding or bonding conductors—whether insulated or bare—must be included in total conductor area. Use Table 5 area for insulated grounds and Table 8 area for bare copper grounds (both options are built into the insulation dropdown above).

When does the 60% conduit nipple fill exception apply?

Under NEC Chapter 9 Note 4, when conduit or tubing nipples between boxes, cabinets, or enclosures do not exceed 24 inches (600 mm) in length, conductors are permitted to occupy up to 60% of the total cross-sectional area, and Table 310.15(C)(1) bundling ampacity derating does not apply.