Ohm's Law & NEC Continuous Load Sizing LOCAL SOLVER · ZERO LOGIN

Watts to Amps & Amps to Watts Calculator

Bidirectional Watts to Amps & Amps to Watts converter for DC, 120V/240V 1-phase, and 3-phase AC with 80% NEC limits.

Power & Current Inputs

DC · 1-PH · 3-PH
DIRECTION
CURRENT TYPE
Enter a voltage between 1 and 15,000 V.
Enter a value between 0 and 10,000,000.
1.0 resistive heaters, 0.8–0.9 motors (ignored in DC)
Enter a power factor between 0.10 and 1.00.

CH-4 · Live Power Conversion

OHM'S LAW · 80% CONT.
CONVERTED OUTPUT
12.50 Amps
SYSTEM SUPPLY 120 V 1-PH AC PF 1.00 · θ 0.0° ACTIVE EQUATION TELEMETRY I = 1500 W / (120 V × 1.00) REAL 1500 W APPARENT 1500 VA NEC 80% CONT: 1200 W · MIN BREAKER 15.6 A COMPUTED CURRENT 12.50 A 1.500 kW 1500.0 VA TOTAL
Real Power
1500.0 W (1.500 kW)
Line Current
12.50 A
Apparent (VA)
1500.0 VA
NEC Continuous
15.63 A min breaker
A 1500W space heater on 120V draws 12.50 A—already exceeding the 12.0 A (1,440 W) NEC 80% continuous load limit of a standard 15A household breaker if run continuously for 3+ hours.

Watts to Amps Quick-Reference Chart (12V DC, 24V DC, 120V AC, 240V AC)

Exact resistive currents (PF = 1.0) for common US appliances, solar batteries, and heating elements from 100 W to 5,000 W.

Common Wattages Converted to Amps (PF = 1.0)
Power (Watts) 12V DC 24V DC 120V AC (1-Ph) 240V AC (1-Ph)
100 W 8.33 A 4.17 A 0.83 A 0.42 A
300 W 25.00 A 12.50 A 2.50 A 1.25 A
400 W 33.33 A 16.67 A 3.33 A 1.67 A
500 W 41.67 A 20.83 A 4.17 A 2.08 A
600 W 50.00 A 25.00 A 5.00 A 2.50 A
1,000 W 83.33 A 41.67 A 8.33 A 4.17 A
1,200 W 100.00 A 50.00 A 10.00 A 5.00 A
1,500 W 125.00 A 62.50 A 12.50 A 6.25 A
1,800 W 150.00 A 75.00 A 15.00 A 7.50 A
2,000 W 166.67 A 83.33 A 16.67 A 8.33 A
3,000 W 250.00 A 125.00 A 25.00 A 12.50 A
4,500 W 375.00 A 187.50 A 37.50 A 18.75 A
5,000 W 416.67 A 208.33 A 41.67 A 20.83 A

Amps to Watts by Standard US Circuit Breaker (100% vs. NEC 80% Continuous)

NEC 210.20(A) limits continuous loads (running 3 hours or more) to 80% of standard overcurrent device rating unless the breaker is specifically listed for 100% continuous operation.

Standard US Branch Circuit & Feeder Wattage Capacities
Breaker Rating 120V Max (100%) 120V Cont. (80%) 240V Max (100%) 240V Cont. (80%)
15 A Circuit 1,800 W 1,440 W 3,600 W 2,880 W
20 A Circuit 2,400 W 1,920 W 4,800 W 3,840 W
30 A Circuit 3,600 W 2,880 W 7,200 W 5,760 W
40 A Circuit 4,800 W 3,840 W 9,600 W 7,680 W
50 A Circuit 6,000 W 4,800 W 12,000 W 9,600 W
60 A Circuit 7,200 W 5,760 W 14,400 W 11,520 W
100 A Circuit 12,000 W 9,600 W 24,000 W 19,200 W

Formulas & Power Factor Notes

Watts ↔ Amps Equations

DC: I = P / V | P = V × I 1-Ph AC: I = P / (V × PF) | P = V × I × PF 3-Ph AC: I = P / (√3 × V_LL × PF) | P = √3 × V_LL × I × PF

Limitations

  • Watts vs. Volt-Amps (VA): Circuit breakers and wire ampacity respond to total current (VA), not just real watts. Always enter power factor < 1.0 for inductive motors, compressors, and fluorescent/LED drivers per NFPA 70 (NEC).
  • Wire gauge & voltage drop: Once you know load amperes, size conductors in our NEC Wire Size Calculator and verify long-run line loss in the NEC Voltage Drop Calculator.

Field Questions & NEC Notes

How many amps is 1500 watts at 120 volts?

At 120V AC with unity power factor (PF = 1.0, resistive heat), 1500 watts draws exactly 12.50 amps (1500 ÷ 120 = 12.5 A). Because a 15A breaker is limited to 12A (1,440W) for continuous loads running 3 hours or longer, a 1500W space heater leaves minimal headroom for other devices on the same 15A branch circuit.

How many watts can a 15-amp or 20-amp 120V US breaker safely handle?

A 15A 120V circuit has a maximum trip ceiling of 1,800 W and an NEC 80% continuous limit of 1,440 W. A 20A 120V circuit has a 100% ceiling of 2,400 W and an 80% continuous limit of 1,920 W.

Why do 12V DC inverter amp calculations exceed Watts ÷ 12?

Pure DC load current is I = W ÷ 12 (so 1000W = 83.33 A at 12.0V). When powering a 120V AC load through a 12V battery inverter, include inverter efficiency (typically 85%–90%) and low-battery voltage sag (~10.5V–11.5V), which increases actual battery-side DC current to roughly 1000 ÷ (11.5 × 0.88) ≈ 99 A.