NEC Conduit Fill Chart (Annex C)
Interactive NEC 2026 Annex C conduit fill chart for EMT (C.1), PVC 40 (C.11), PVC 80 (C.10), RMC (C.9), IMC, and FMC.
| Wire Size | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 12 | 22 | 35 | 61 | 84 | 138 | 241 | 364 | 476 | 608 |
| 12 AWG | 9 | 16 | 26 | 45 | 61 | 101 | 176 | 266 | 347 | 443 |
| 10 AWG | 5 | 10 | 16 | 28 | 38 | 63 | 111 | 167 | 219 | 279 |
| 8 AWG | 3 | 6 | 9 | 16 | 22 | 36 | 64 | 96 | 126 | 161 |
| 6 AWG | 2 | 4 | 7 | 12 | 16 | 26 | 46 | 69 | 91 | 116 |
| 4 AWG | 1 | 2 | 4 | 7 | 10 | 16 | 28 | 43 | 56 | 71 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 24 | 36 | 47 | 60 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 20 | 30 | 40 | 51 |
| 1 AWG | 1 | 1 | 1 | 4 | 5 | 8 | 15 | 22 | 29 | 37 |
| 1/0 AWG | 1 | 1 | 1 | 3 | 4 | 7 | 12 | 19 | 25 | 32 |
| 2/0 AWG | 0 | 1 | 1 | 2 | 3 | 6 | 10 | 16 | 20 | 26 |
| 3/0 AWG | 0 | 1 | 1 | 1 | 3 | 5 | 8 | 13 | 17 | 22 |
| 4/0 AWG | 0 | 1 | 1 | 1 | 2 | 4 | 7 | 11 | 14 | 18 |
| 250 kcmil | 0 | 0 | 1 | 1 | 1 | 3 | 6 | 9 | 11 | 15 |
| 300 kcmil | 0 | 0 | 1 | 1 | 1 | 3 | 5 | 7 | 10 | 13 |
| 350 kcmil | 0 | 0 | 1 | 1 | 1 | 2 | 4 | 6 | 9 | 11 |
| 400 kcmil | 0 | 0 | 0 | 1 | 1 | 1 | 4 | 6 | 8 | 10 |
| 500 kcmil | 0 | 0 | 0 | 1 | 1 | 1 | 3 | 5 | 6 | 8 |
Quick Comparison Across EMT, PVC Sch 40, PVC Sch 80 & RMC (THHN/THWN-2)
Side-by-side maximum conductor counts for common 3/4" and 2" trade sizes. Notice how heavy-wall PVC Schedule 80 reduces conductor counts compared to EMT and PVC Schedule 40.
| Wire Size | 3/4" EMT | 3/4" PVC 40 | 3/4" PVC 80 | 3/4" RMC | 2" EMT | 2" PVC 80 |
|---|---|---|---|---|---|---|
| 14 AWG | 22 | 21 | 17 | 22 | 138 | 118 |
| 12 AWG | 16 | 15 | 12 | 16 | 101 | 86 |
| 10 AWG | 10 | 9 | 7 | 10 | 63 | 54 |
| 8 AWG | 6 | 5 | 4 | 6 | 36 | 31 |
| 6 AWG | 4 | 4 | 3 | 4 | 26 | 22 |
| 4 AWG | 2 | 2 | 1 | 2 | 16 | 14 |
| 2 AWG | 1 | 1 | 1 | 1 | 11 | 10 |
| 1/0 AWG | 1 | 1 | 1 | 1 | 7 | 6 |
| 3/0 AWG | 1 | 1 | 1 | 1 | 5 | 4 |
| 4/0 AWG | 1 | 1 | 0 | 1 | 4 | 3 |
Dedicated Raceway Charts & Code Boundaries
Specialized NEC Charts & Calculators
- PVC Schedule 40 vs. Schedule 80 Fill Chart — full internal diameter and capacity delta between Table C.11 and Table C.10.
- EMT Conduit Fill Chart (Table C.1) — dedicated EMT reference with 3/4" EMT field lookup presets.
- Mixed-Wire Conduit Fill Calculator — add different wire sizes and bare copper EGC with SVG cross-section verification.
- NEC Voltage Drop Calculator — verify whether long conduit runs require upsizing conductors beyond ampacity before finalizing raceway trade size.
NEC Annex C Limits
- All values follow NFPA 70 (NEC) Chapter 9 Table 1 (53% 1 wire / 31% 2 wires / 40% 3+ wires) and Chapter 9 Note 7 (≥ 0.80 fractional round-up).
- Compact stranded aluminum conductors (NEC Table 5A) have slightly smaller cross-sectional areas than standard stranded copper/aluminum listed here.
- For workplace electrical installation requirements covering raceways and conductor protection, refer to OSHA 29 CFR 1910.305.
Field Questions & NEC Notes
When can I use the NEC Annex C conduit fill chart instead of calculating square inches?
You can read directly from NEC Annex C tables only when every conductor in the conduit has the exact same AWG/kcmil size and the exact same insulation type (for example, all 12 AWG THHN). The moment you include a smaller equipment grounding conductor or mix circuit sizes, you must sum individual Table 5 areas in our Mixed Conduit Fill Calculator.
Why does Annex C sometimes allow one extra wire beyond raw 40% area division?
Per NEC Chapter 9 Note 7, when dividing allowable 40% conduit area by a single conductor's area yields a decimal of 0.80 or greater, you round up to the next whole number. For example, 3/4" EMT (0.2132 in² at 40%) divided by 8 AWG THHN (0.0366 in²) equals 5.825—which rounds up to 6 conductors.
Does Annex C already account for NEC 310.15(C)(1) bundling derating?
No. Annex C measures physical cross-sectional space only. Placing 16 pieces of 12 AWG THHN inside a 3/4" EMT conduit is physically legal, but if all 16 are current-carrying conductors, Table 310.15(C)(1) reduces each wire's ampacity to 50% (15 A from the 90°C 30A base).