3-Phase Power Calculator (kW, kVA & Amps)

3-phase power calculator for US 208V, 240V, 480V, and 600V systems solving kW, kVA, kVAR, amps, and shaft HP.

3-Phase System Inputs

PRESETS M1–M4
SOLVE FROM
VOLTAGE REF
Enter a 3-phase voltage between 1 and 35,000 V.
Enter a value between 0 and 100,000.
Enter a power factor between 0.10 and 1.00.
Enter an efficiency between 10% and 100%.

CH-5 · Live 3-Phase Power Triangle

WYE / DELTA · √3
CALCULATED 3-PHASE OUTPUT
42.40 kW / 49.88 kVA
P = 42.40 kW Q = 26.28 kVAR S = 49.88 kVA θ 31.8° 3-PHASE PHASOR TELEMETRY (√3) LINE CURRENT 60.00 A WYE VOLTAGES 480.0V L-L / 277.1V L-N POWER FACTOR cos θ = 0.85 SHAFT OUTPUT 52.31 HP (92% EFF)
P = √3 × 480.0 V × 60.00 A × 0.85 ÷ 1000 = 42.40 kW
Real Power (P)
42.40 kW
Apparent (S)
49.88 kVA
Reactive (Q)
26.28 kVAR
Line Current
60.00 A
Wye Voltages
480.0V / 277.1V
Shaft HP
52.31 HP (θ 31.8°)

208V vs. 480V 3-Phase Line Current Reference Table (5–200 kW)

Compare line current on standard US 208V commercial and 480V industrial 3-phase systems at both 0.85 inductive motor power factor and 1.0 resistive power factor.

Balanced 3-Phase Line Amperes by kW Rating
Real Power kVA (@ 0.85 PF) 208V (0.85 PF) 208V (1.0 PF) 480V (0.85 PF) 480V (1.0 PF)
5 kW 5.9 kVA 16.3 A 13.9 A 7.1 A 6.0 A
10 kW 11.8 kVA 32.7 A 27.8 A 14.2 A 12.0 A
15 kW 17.6 kVA 49.0 A 41.6 A 21.2 A 18.0 A
25 kW 29.4 kVA 81.6 A 69.4 A 35.4 A 30.1 A
50 kW 58.8 kVA 163.3 A 138.8 A 70.8 A 60.1 A
75 kW 88.2 kVA 244.9 A 208.2 A 106.1 A 90.2 A
100 kW 117.6 kVA 326.6 A 277.6 A 141.5 A 120.3 A
150 kW 176.5 kVA 489.8 A 416.4 A 212.3 A 180.4 A
200 kW 235.3 kVA 653.1 A 555.1 A 283.0 A 240.6 A

3-Phase Equations & Balanced-Load Assumptions

Standard 3-Phase Identities

S (kVA) = (√3 × V_LL × I_line) / 1000 P (kW) = S × PF = (√3 × V_LL × I_line × PF) / 1000 Q (kVAR)= √(S² − P²) | V_LL = √3 × V_LN

Once line current is solved, verify 3-phase feeder drop in our NEC Voltage Drop Calculator (using the √3 steel/PVC impedance model) and size conductors in the NEC Wire Size Calculator.

Scope Limitations

  • Balanced loads assumed: Unbalanced single-phase loads tapped off a 3-phase Wye panel require per-phase current analysis and neutral sizing per NFPA 70 (NEC) §220.61.
  • Non-linear harmonic loads: VFDs, UPS rectifiers, and LED lighting introduce total harmonic distortion (THD) that lowers true power factor below displacement cos θ; also verify motor efficiency standards via the US DOE Electric Motors guidance.

Field Questions & NEC Notes

Why does the 3-phase power formula multiply by √3 (1.732) instead of 3?

Total 3-phase power equals 3 × VLN × Iphase × PF. In a balanced Wye system, line-to-line voltage is VLL = √3 × VLN, so substituting VLN = VLL / √3 reduces 3 / √3 to exactly √3 (1.73205). The same √3 × VLL × Iline identity holds for balanced Delta loads.

What is the difference between kW, kVA, and kVAR in a 3-phase system?

kW (Real Power) performs actual mechanical or heating work. kVA (Apparent Power) determines conductor and transformer current loading (kVA = kW ÷ PF). kVAR (Reactive Power) sustains magnetic fields in motors and transformers (kVAR = √(kVA² − kW²)).

Should I enter 277V or 480V on a US 480Y/277V commercial panel?

Select Line-to-Line (VLL) and enter 480 V (or select Line-to-Neutral and enter 277 V—the calculator automatically computes the matching 480.0 V line-to-line voltage using √3).