NEC Wire Size & AWG Calculator
NEC 2026 wire gauge calculator solving separate 125% terminal ampacity, thermal derating, and Chapter 9 voltage drop.
Load, Thermal & Run Inputs
PRESETS M1–M4- Design Current (125%)
- 60.0 A
- Min AWG (Ampacity)
- 6 AWG (65.0 A)
- Min AWG (Volt Drop)
- 8 AWG
- Thermal Derating
- 100% (1.00 × 1.00)
- Final Voltage Drop
- 3.76 V (1.57%)
- Derated Ampacity
- 65.0 A
NEC 2026 Table 310.16 Allowable Ampacities (30°C Base)
Allowable ampacities for not more than three current-carrying conductors in a raceway, cable, or earth at 30°C (86°F) ambient temperature, with NEC 240.4(D) small-conductor OCPD limits noted.
| Size | Cu 60°C | Cu 75°C | Cu 90°C | Al 60°C | Al 75°C | Al 90°C | 240.4(D) Cap |
|---|---|---|---|---|---|---|---|
| 14 AWG | 15 A | 20 A | 25 A | — | — | — | 15 A Cu |
| 12 AWG | 20 A | 25 A | 30 A | 15 A | 20 A | 25 A | 20 A Cu |
| 10 AWG | 30 A | 35 A | 40 A | 25 A | 30 A | 35 A | 30 A Cu |
| 8 AWG | 40 A | 50 A | 55 A | 35 A | 40 A | 45 A | Table |
| 6 AWG | 55 A | 65 A | 75 A | 40 A | 50 A | 55 A | Table |
| 4 AWG | 70 A | 85 A | 95 A | 55 A | 65 A | 75 A | Table |
| 3 AWG | 85 A | 100 A | 115 A | 65 A | 75 A | 85 A | Table |
| 2 AWG | 95 A | 115 A | 130 A | 75 A | 90 A | 100 A | Table |
| 1 AWG | 110 A | 130 A | 145 A | 85 A | 100 A | 115 A | Table |
| 1/0 AWG | 125 A | 150 A | 170 A | 100 A | 120 A | 135 A | Table |
| 2/0 AWG | 145 A | 175 A | 195 A | 115 A | 135 A | 150 A | Table |
| 3/0 AWG | 165 A | 200 A | 225 A | 130 A | 155 A | 175 A | Table |
| 4/0 AWG | 195 A | 230 A | 260 A | 150 A | 180 A | 205 A | Table |
| 250 kcmil | 215 A | 255 A | 290 A | 170 A | 205 A | 230 A | Table |
| 300 kcmil | 240 A | 285 A | 320 A | 195 A | 230 A | 260 A | Table |
| 350 kcmil | 260 A | 310 A | 350 A | 210 A | 250 A | 280 A | Table |
| 400 kcmil | 280 A | 335 A | 380 A | 225 A | 270 A | 305 A | Table |
| 500 kcmil | 320 A | 380 A | 430 A | 260 A | 310 A | 350 A | Table |
Dual-Constraint Sizing Logic & Boundaries
Governing Wire Selection Steps (NEC 210.19(A)(1))
Check 1 (Terminal / Continuous): min(Amp_term, Cap_240.4D) ≥ I_load × (1.25 if continuous else 1.0)
Check 2 (Thermal / Bundling): min(Amp_ins × F_ambient × F_bundle, Amp_term) ≥ I_load
Governing AWG = max(AWG_ampacity, AWG_voltage_drop)
Per NFPA 70 (NEC) §210.19(A)(1) and §215.2(A)(1), the 125% continuous-load factor is checked before ambient/bundling adjustment, and the thermally adjusted ampacity is verified against 100% actual operating load. Inspect detailed impedance and Copper vs. Aluminum cost tradeoffs in our NEC Voltage Drop Calculator.
Scope Limitations
- Single conductor sets only: Loads requiring above 500 kcmil must be evaluated for parallel sets per NEC 310.10(G).
- Rooftop conduit sunlight adder: If raceways sit within 7/8" of a rooftop, verify local NEC 310.15(B)(2) ambient temperature elevation before choosing ambient °C.
- Motor circuits (Article 430): Size motor branch conductors using NEC Table 430.248 / 430.250 FLC rather than nameplate FLA, and confirm installation rules under OSHA 29 CFR 1910.303.
Field Questions & NEC Notes
Why can't I use the 90°C THHN ampacity column directly on a 60A circuit breaker?
Under NEC 110.14(C), conductor terminations on breakers and panel lugs rated 100A or less are generally limited to 60°C unless the equipment is explicitly listed and marked for 75°C (most modern breakers are marked 60°C/75°C). You may use the 90°C column as the starting point for ambient and bundling derating, provided the final ampacity never exceeds the 75°C terminal rating.
Why does a 48A EV charger require 6 AWG copper THHN or 4 AWG NM-B Romex?
An EV charger is a continuous load (NEC 625.41), requiring 48 A × 1.25 = 60 A minimum conductor and breaker sizing. In the 75°C column (THHN/THWN-2 in conduit), 6 AWG copper is rated 65 A (sufficient for 60 A). In NM-B cable, NEC 334.80 restricts ampacity to the 60°C column, where 6 AWG copper is only 55 A—forcing an upsize to 4 AWG NM-B (70 A) for a hardwired 48A charger.
Does this calculator apply NEC 310.12 residential 83% service sizing?
No—this tool uses conservative general-purpose NEC Table 310.16 ampacities for all feeders and branch circuits. For one- and two-family dwelling main power feeders and services (100A–400A), NEC 310.12 permits an 83% sizing allowance (e.g., 4/0 Aluminum for a 200A dwelling service instead of 250 kcmil).